This is close, and I'd grant that limit trips are associated with longer run times. But in principle continuous furnace run time shouldn't cause a high limit trip. The limit is mainly to protect the heat exchanger from damage. The primary cause is usually low/reduced airflow, although bad sensors are also common.

A high limit trip will generally cycle the furnace off for a time period. Somewhere between 3-5 off cycles will result in lockout and the furnace will stay off. The control for this is more likely to reside in the furnace board vs an aftermarket ui.

I'm the author of the article. The dual manometer suggestion below is excellent. I use external static pressure to calculate airflow using manufacturer tables quite frequently. It's fast and only slightly less accurate than using an expensive flow grid. I also use a manometer to measure pressure drops across filters and AC coils quite a bit.

I'd add a tool for measuring temperature, ideally a digital psychrometer, but even something that just measures dry bulb is useful for heating and bad AC failure.

Finally a multimeter, ideally with clamp on amp readings.